直流蓄电池充放电试验检查汇报 试验项目直流蓄电池充放电试验页次试验部门电气班安装部位主控室1/5蓄电池组别Ⅰ 测量仪器名称型号仪器编号测量环境万用表FLUKE115C温度26.3℃智能型蓄电池放电仪BFD220R20湿度60%红外线点温枪雷泰试验日期. 08.23一、放电记录放电时间(H)12345678910电流(A)20202020202020202020电压(V)235.3210.1208.7207.1205.4203.5201.5199.0195.6192.5编号初始值(V)(V)(V)(V)(V)(V)(V)(V)(V)(V)12.1632.1032.1232.1091.9931.9771.9611.9421.9191.8921.87022.1652.1322.1222.1081.9911.9761.9591.9401.9171.8891.86732.1632.1352.1252.1111.9951.9791.9631.9441.9211.8931.87242.1652.1312.1202.1061.9881.9721.9551.9351.9101.8801.85552.1632.1382.1302.1182.2031.9891.9741.9561.9361.9131.89562.1732.1392.1302.1172.0011.9871.9711.9521.9301.9061.86672.1652.1412.1332.1222.2071.9941.9801.9631.9441.9231.90682.1732.1382.1282.1141.9971.9831.9661.9461.9241.8991.87892.1662.1372.1282.1162.2011.9871.9721.9541.9331.9101.892102.1662.1392.1312.1192.2041.9901.9751.9581.9381.9151.898112.1632.1422.1352.1252.2122.2011.9891.9741.9581.9401.926122.1642.1382.1292.1172.2021.9891.9731.9551.9351.9111.893132.1622.1312.1192.1051.9871.9701.9531.9321.9071.8761.850142.1652.1432.1362.1262.0122.0001.9861.9711.9541.9351.921152.1652.1412.1342.1222.0081.9941.9801.9641.9451.9241.908162.1692.1362.1242.1101.9921.9761.9591.9391.9151.9871.864172.1642.1402.1322.1202.0061.9921.9771.9611.9421.9211.905182.1572.1292.1172.1021.9851.9681.9511.9301.9051.8751.849192.1602.1372.1292.1162.0001.9861.9701.9531.9321.9071.888202.1612.1382.1292.1162.0011.9861.9711.9541.9331.9081.889212.1642.1382.1282.1141.9981.9841.9671.9471.9241.8981.876222.1612.1412.1342.1232.0101.9971.9831.9671.9491.9301.916232.1582.1292.1162.1011.9831.9671,9481.9261.8991.8661.837242.1602.1382.1302.1182.0031.9901.9751.9581.9381.9161.898252.1602.1322.1232.1101.9941.9801.9641.9441.9221.8961.876262.1632.1382.1302.1182.0031.9891.9741.9561.9351.9121.893272.1662.1422.1362.1252.0122.0001.9861.9701.9531.9341.920282.1622.1372.1292.1162.0011.9871.9711.9531.9331.9101.891292.1582.1322.1292.1091.9921.9771.9601.9411.9181.8911.869302.1652.1412.1342.1232.0091.9961.9821.9671.9491.9281.913试验项目营地直流蓄电池充放电试验页次试验部门电气班安装部位主控室2/5蓄电池组别Ⅱ测量仪器名称型号仪器编号测量环境万用表FLUKE115C温度26.3℃智能型蓄电池放电仪BFD220R20湿度60%红外线点温枪雷泰试验日期.08.23一、放电记录放电时间(H)12345678910电流(A)20202020202020202020电压(V)211.3210.1208.7207.1205.4203.5201.5199.0195.6192.5编号初始值(V)(V)(V)(V)(V)(V)(V)(V)(V)(V)312.1622.0402.0322.0202.0051.9921.9771.9611.9411.9191.902322.1672.0362.0272.0131.9971.9821.9661.9481.9261.9011.881332.1572.0342.0242.0111.9961.9801.9641.9461.9241.8981.878342.1682.0422.0342.0212.0071.9921.9771.9601.9401.9171.900352.1702.0452.0372.0252.0111.9981.9831.9671.9491.9281.912362.1622.0412.0332.0222.0081.9941.9801.9641.9461.9251.909372.1632.0412.0342.0222.0081.9961.9801.9641.9441.9231.907382.1632.0382.0282.0162.0001.9871.9701.9521.9311.9071.888392.1592.0382.0292.0162.0001.9861.9691.9501.9281.9041.883402.1632.0422.0352.0242.0101.9991.9841.9681.9501.9301.915412.1642.0372.0272.0131.9971.9831.9651.9461.9231.8961.874422.1572.0402.0312.0192.0041.9911.9751.9581.9371.9151.897432.1652.0382.0272.0121.9961.9811.9631.9421.9181.8901.866442.1532.0302.0192.0041.9871.9721.9531.9321.9051.8751.847452.1582.0362.0252.0111.9951.9791.9621.9441.9201.8921.869462.1642.0442.0372.0262.0121.9991.9841.9691.9501.9301.905472.1592.0342.0232.0091.9931.9771.9591.9411.9171.8891.866482.1642.0362.0252.0111.9951.9781.9611.9421.9191.8961.869492.1532.0302.0192.0041.9871.9701.9521.9321.9071.8761.849502.1622.0382.0282.0162.0011.9851.9601.9511.9301.。