1、冷却塔原理及计算冷却塔原理及计算 Cooling Towers: Design and Operation ConsiderationsCooling towers are a very important part of many chemical plants. They represent a relatively inexpensive and dependable means of removing low grade heat from cooling water.Figure 1: Closed Loop Cooling Tower SystemThe make-up water

2、 source is used to replenish water lost to evaporation. Hot water from heat exchangers is sent to the cooling tower. The water exits the cooling tower and is sent back to the exchangers or to other units for further cooling. Types of Cooling TowersCooling towers fall into two main sub-divisions: nat

3、ural draft and mechanical draft. Natural draft designs use very large concrete chimneys to introduce air through the media. Due to the tremendous size of these towers (500 ft high and 400 ft in diameter at the base) they are generally used for water flowrates above 200,000 gal/min. Usually these typ

4、es of towers are only used by utility power stations in the United States. Mechanical draft cooling towers are much more widely used. These towers utilize large fans to force air through circulated water. The water falls downward over fill surfaces which help increase the contact time between the wa

5、ter and the air. This helps maximize heat transfer between the two. Types of Mechanical Draft TowersFigure 2: Mechanical Draft Counterflow Tower Figure 3: Mechanical Draft Crossflow TowerMechanical draft towers offer control of cooling rates in their fan diameter and speed of operation. These towers

6、 often contain several areas (each with their own fan) called cells. Cooling Tower TheoryHeat is transferred from water drops to the surrounding air by the transfer of sensible and latent heat.Figure 4: Water Drop with Interfacial FilmThis movement of heat can be modeled with a relation known as the

7、 Merkel Equation:(1)where:KaV/L = tower characteristicK = mass transfer coefficient (lb water/h ft2)a = contact area/tower volumeV = active cooling volume/plan areaL = water rate (lb/h ft2)T1 = hot water temperature (0F or 0C)T2 = cold water temperature (0F or 0C)T = bulk water temperature (0F or 0C

8、)hw = enthalpy of air-water vapor mixture at bulk water temperature(J/kg dry air or Btu/lb dry air)ha = enthalpy of air-water vapor mixture at wet bulb temperature(J/kg dry air or Btu/lb dry air)Thermodynamics also dictate that the heat removed from the water must be equal to the heat absorbed by th

9、e surrounding air:(2)(3)where:L/G = liquid to gas mass flow ratio (lb/lb or kg/kg)T1 = hot water temperature (0F or 0C)T2 = cold water temperature (0F or 0C)h2 = enthalpy of air-water vapor mixture at exhaust wet-bulb temperature (same units as above)h1 = enthalpy of air-water vapor mixture at inlet

10、 wet-bulb temperature (same units as above) The tower characteristic value can be calculated by solving Equation 1 with the Chebyshev numberical method:(4)Figure 5: Graphical Representation of Tower CharacteristicThe following represents a key to Figure 5: C = Entering air enthalpy at wet-bulb tempe

11、rature, Twb BC = Initial enthalpy driving force CD = Air operating line with slope L/G DEF = Projecting the exiting air point onto the water operating line and then onto thetemperature axis shows the outlet air web-bulb temperatureAs shown by Equation 1, by finding the area between ABCD in Figure 5,

12、 one can find the tower characteristic. An increase in heat load would have the following effects on the diagram in Figure 5: 1. Increase in the length of line CD, and a CD line shift to the right 2. Increases in hot and cold water temperatures 3. Increases in range and approach areasThe increased h

13、eat load causes the hot water temperature to increase considerably faster than does the cold water temperature. Although the area ABCD should remain constant, it actually decreases about 2% for every 10 0F increase in hot water temperature above 100 0F. To account for this decrease, an “adjusted hot

14、 water temperature“ is usd in cooling tower design.Figure 6: Graph of Adjusted Hot Water TemperaturesThe area ABCD is expected to change with a change in L/G, this is very key in the design of cooling towers. Cooling Tower DesignAlthough KaV/L can be calculated, designers typically use charts found

15、in the Cooling Tower Institute Blue Book to estimate KaV/L for given design conditions. It is important to recall three key points in cooling tower design: 1.1. A A changechange inin wetwet bulbbulb temperaturetemperature (due(due toto atmosphericatmospheric conditions)conditions) willwill notnot ch

16、angechange thethe towertower characteristiccharacteristic (KaV/L)(KaV/L) 2.2. A A changechange inin thethe coolingcooling rangerange willwill notnot changechange KaV/LKaV/L 3.3. OnlyOnly a a changechange inin thethe L/GL/G ratioratio willwill changechange KaV/LKaV/LFigure 7: A Typical Set of Tower Characteristic CurvesThe straight line shown in Figure 7 is a plot of L/G vs KaV/L at a const