《常用电气设备需要系数表》由会员分享,可在线阅读,更多相关《常用电气设备需要系数表(3页珍藏版)》请在金锄头文库上搜索。
1、设备名 称Kxcostan设备名 称Kxcostan宾馆总照明0. 350.450.850.62实验室及实习工厂0. 10 0.200. 700.800. 751.02冷冻机房0. 650.750.800.75绞肉机、磨碎机0.700.800. 75锅炉房0. 650.750.750.88医院 (卫生所)电 力0. 400.500.800.75给、排水泵0.800.850.62金工、装配、修理用起重机0.05 0.150.501.73厨房电力0.50 0.700.800.75重型工作起动机0.25 0.35洗衣机房0.65 0.750.501.73小容量试验设0.10 0.250.204.90
2、电力备窗式空调器0.70 0.800.800.75电焊机0.350.60.71.02 1.33卫生通风机0.65 0.700.800.75单头焊接义压器0.350.352.68生产通风机0.75 0.850.80 0.850.62 0.75多头焊接义压器0.400.352.68电梯0.600.701.02混凝土及砂浆搅拌机0.65 0.700.651.17干烤箱、加热器0.40 0.6010破碎机、筛、泥浆机、砾石洗条机0.700.701.02红外0.85 10施工用起重0.250.701.02设备0.90机、挖土机、升降机常用电气设备的需要系数Kx及cos、tan 值1)用电设备组的计算负荷有功功率Pjs =Kx Ps (KW无功功率Qjs = Pjs tan小 (KV A)视在功率Sjs = Pjs/cos 小 (KVA2)配电干线的计算负荷。有功功率Pjs =Kt EKx Ps(KW无功功率Qjs = Kt( EKx Ps tan 小)(KV A)视在功率Sjs = (P2js+ Q2js)?(KV- A)则计算电流为 Ijs= Sjs /,3 VN3)电力变压器的有功损耗和无功损耗分别为: PB =0.02 Sjs(KW QB =0.08 Sjs (KV A)