1、HPMV-DN Medium-voltage Soft StarterInstruction Manual1SafetyRead this manual carefully before operating the equipment and follow the instructions. Installation, operation and maintenance should be strictly accordance with this manual, national codes and good practice. Installation or operation not p

2、erformed in strict accordance with these instructions will void manufacturers warranty. Disconnect all power inputs before servicing the soft-starter and/or the motor. After installation, check and verify that no parts (bolts, washers, etc) have fallen into the power Section (IP00).Attention1.This p

3、roduct was designed for compliance with IEC 947-4-2 for class A equipment. 2.For further information see Technical SpecificationWarningsInternal components and P.C.Bs are at main potential when the HPMV -DN is connected to main voltage. This voltage is extremely dangerous and will cause death or sev

4、ere injury if contacted. When HPMV-DN is connected to the main voltage, even if control voltage is disconnected and motors is stopped, full voltage may appear on starters output and motors terminals. Unit must be grounded to ensure correct operation, safety and prevent damage. Check that Power Facto

5、r capacitors are not connected to the output side of the soft starter and confirm that they are connected upstream to the line contractorThe company reserves the right to make any improvements Or modifications to its products without prior notice2Table of ContentsPageSubject 3Starter Selection 4-5In

6、stallation 6-7Internal Setting 8-9Control Terminals 10Control Terminals Option Boards 11-12Control Wiring 13Wiring Diagrams 14Wiring Diagrams Diesel Generator 15-16Wiring Diagrams Communication 17-18Start resistance 20 KO Check for no voltage on terminals U, V, W (from parallel system or an independ

7、ent by- pass). SCRs may fail due to:* High short current not protected by proper fuses. * High voltage spikes not protected by proper external Varistors. * Frequent starting at maximum conditions or fault conditions.OVER TEMPERATUREHeat-sink over-temperature trips the starter when heat-sink temperat

8、ure rises above 85C. Improve cooling or use a by-pass control. Check that motor starting is not too frequent.EXTERNAL FAULT 1&2Trips the starter when a N.O contact between terminals 19-21 closes for over two seconds. Check contact position and cause of closure.WRONG PARAMETERSParameters not transfer

9、red from RAM to EEPROM or vice versa. After replacing the EPROM with a new software version or after power up, press Reset, than Mode and simultaneously and save the default parameters by pressing Store and Mode simultaneously. (If Fault LED is on, press Reset after storing parameters).* NOTES:1.Whe

10、n operating in generator mode, shorted SCR and wrong connection faults are not active. 2.Upon any fault, check first Fiber/Optic leads and confirm correct lead insertion (full 18mm).Technical Specification39General Information: Supply Voltage . Line to Line 2300V, 3300V, 4160V, 6900V 10000V(other vo

11、ltages TBD) + 10%- 15% P.I.V ratings. For 2300V, PIV is 6900V For 3300V, PIV is 9900V For 4160V, PIV is 12,500V For 6900V, PIV is 19,500V For 10000V, PIV is 26,000V Frequency. 45 65 Hz (Fixed or while frequency varies) Control Supply . 110-230V (to be specified) +10% - 15% Control inputs & Outputs .

12、 Either same as Control Supply or by special order 24-230V AC/DC (to be specified) Load. Thee phase, three wire, squirrel cage induction motor.Start-Stop Parameters: Starter FLC. Starter Full Load Current according to Selector Guide Motor FLA. Motor Full Load Ampere 50-100% of starter FLC Pump Contr

13、ol Curves. 6 field selectable curves preventing over-pressure during start and water hammer during stop. Pulse Start Duration. A pulse of 80% Un, for an adjustable time 0.1-2 Sec, for starting high friction loads Initial Voltage. 10-50% Un (*5-85%), 5% - by special order Current Limit. 100-400% of M

14、otor FLA (*100-500%) Acceleration Time . 1-30 Sec (*1-90 sec) Deceleration Time . 1-30 Sec (*1-90 sec, not in Dual Adjust) Dual Adjustments. Secondary start stop characteristic for: Motor FLA, Initial Voltage, Current Limit, Acceleration Time and Deceleration Time. Tacho and Linear Acceleration. 12 field selectable curves defining Tacho Feedback gain improving linearity. * Consult FactoryMotor Protection: Too many starts. Maximum number of starts range Off or 1-10, du