1、Aquatrol Profile Manager (with HC900)Error! Reference source not found.Protective EnclosureThe electronics of the Profile Manager are housed in a floor mounted cabinet that has a protection rating of NEMA 12. Cabinets include a cable base for easy cable entry. For further details, see Error! Referen

2、ce source not found. on page 33. Power Conversion DevicesSingle phase AC power enters the Aquatrol Profile Manager through connection to the main circuit breaker, usually located on terminal strip TS1. Circuit breakers and fuses within the Profile Manager distribute power and protect the various dev

3、ices being powered by the Profile Manager.Three-phase AC power enters the Aquatrol Profile Manager and is distributed to one or more 24VDC power supplies to provide 24VDC power for the actuators. They may also be used to supply power for various interlock devices and signals.Protection DevicesThe el

4、ectronics included in the Profile Manager are electrically protected with both fuses and circuit breakers. The power supplies themselves have a regulated output voltage and are electronically protected against overload and short circuiting. Communications DevicesWhere applicable, Profile Managers wi

5、ll include an RS232/RS485 converter for control systems using serial communication links. This RS232/RS485 converter converts the RS232 output from the Industrial PCs serial port into RS485 communications for the control system. Industrial PC (optional)Profile Managers which require a communications

6、 interface other than Modbus TCP, or Modbus RTU will be equipped with an industrial PC to act as a protocol converter between the Supervisory Control System and the HC900 Controller.This PC can be configured to communicate to the Supervisory Control System using either ODX protocol, or an OPC interf

7、ace.UtilitiesIntroductionThe Profile Manager is shipped factory configured to operate with the specified Supervisory Control System. During system installation and maintenance, it may be necessary to change some of the configuration and tuning values used by the system, or to replace components of t

8、he Actuator control system. Various utilities are required to assist with these changes.Hybrid Control DesignerHybrid Control Designer is a software utility designed specifically for the HC900 series of controllers. Its major functions include: Viewing and modifying block logic Viewing and modifying

9、 I/O configuration Changing the network parameters of the HC900 processorWindows Remote DesktopWindows Remote Desktop, a standard feature with Windows XP, is used to configure a Industrial PC when connecting a monitor and keyboard directly to the processor is not possible. It can be used for the fol

10、lowing functions: Modifying Industrial PC communications parameters Configuring a replacement Industrial PCPersonal ComputerAll of the utilities previously described in this chapter require a personal computer. The minimum requirements for this PC are: CPU: Pentium, 300MHz Operating System: Windows

11、2000, Windows XP Display Color: Minimum resolution (256 color x 1024 x 768 resolution) Pointing Device: Mouse, Trackball or compatible device RAM: 128MB Minimum Removable Disk Drive: CD ROM Drive Ports: EthernetCommon TasksThis chapter contains descriptions of how to perform common tasks for CDWeb s

12、ystems. Basic instructions are given for loading and communicating with the HC900 controller, but for a fuller understanding of its capabilities and features, reading the HC900 documentation is recommended. Before attempting these procedures, ensure that the software tools have been properly install

13、ed on a suitable maintenance computer.Establish a Network Connection to the HC900To modify settings, logic, or configuration on the HC900, first establish a connection between the maintenance PC running Hybrid Control Designer and the HC900 Controller. To establish this connection:1. Connect a strai

14、ght through Ethernet cable between the PC and the HC900.2. Inside Hybrid Control Designer, open the configuration file (*.cde). If you do not have the .cde for the system, see Section 0.3. Select the Utilities tab.4. Under the PC Port Setup menu click on Network.5. If the IP address of the HC900 doe

15、s not appear in the list click on Add, otherwise proceed to step 7.6. Enter the HC900 IP address7. Highlight the address of the HC900 in the list and click on Loop Back to test communications.Modify the TCP/IP Settings of the HC900To change the IP address or any other TCP/IP settings of the HC900 Hy

16、brid Controller:1. Create a backup copy of the existing HC900 logic and configuration (see Section 0).2. Establish a network connection with the HC900 Controller. 3. Add the new IP address for the controller by clicking on Network in PC Port Setup.4. Add the desired new IP address. 5. From the Utilities screen, select Set Controller Networ