《APCUPS电源Silcon客户工程师培训》由会员分享,可在线阅读,更多相关《APCUPS电源Silcon客户工程师培训(90页珍藏版)》请在金锄头文库上搜索。

1、跳转到第一页Silcon 客户工程师培训客户工程师培训跳转到第一页 DP300E SeriesThe product family offers.FROM10 to 480 kVAin one unit跳转到第一页Product OfferingAPC SILCON SERIES 10 - 480kW 380/400/415V - 50/60HzAPC Silcon 10kW Series600mm for external batt600mm for 1 x BPI800mm for 2 x BPI1000mm for 3 x BPI600mm w/1 x BPI800mm w/2 x BP

2、I1000mm w/3 x BPIAPC Silcon 20kW Series600mm for external batt600mm for 1 x BPI800mm for 2 x BPI1000mm for 3 x BPI600mm w/1 x BPI800mm w/2 x BPI1000mm w/3 x BPIAPC Silcon 40kW Series800mm for external batt1000mm w/2 x BPI1000mm for 2 x BPIBPI = Battery Pack I (64 batteries x 12V/7Ah)APC Silcon 60kW

3、Series800mm for external battAPC Silcon 80kW Series800mm for external battAPC Silcon 120kW Series 1125mm for external battAPC Silcon 160kW Series 1125mm for external battAPC Silcon 240kW Series 1600mm for external battAPC Silcon 320kW Series 1600mm for external battAPC Silcon 480kW Series 1900mm for

4、 external batt跳转到第一页SKU Translation GuideSL - APC Silcon SeriesSBB - Battery Breaker Box (not available yet!)SBP - Service Bypass PanelSLB - Battery Cabinets (not available yet!)SLBATT - Battery Open Rack (not available yet!)SLT - Transformers (not available yet!)跳转到第一页Example: SL10KHB0 - SL40KHB2SL

5、shows that it is an APC Silcon UPS10shows the sizeKshows that the size is in kilowattHis 400VB0means no internal batteries,battery drawers and cables for 1 x stringB2means with internal batteries, 2 x BPIAPC Silcon Series SKU# Configuration跳转到第一页SKU Translation GuideSL 10 K H B 2APC SILCON SERIES10k

6、 = 10,000VAe.g. k for kilo and m for megaH = 380/400/415V2 = Number of battery strings includedB = Prepared for batteries, battery drawers and cables included跳转到第一页SL 20 K G B 0APC SILCON SERIES20k = 20,000VAe.g. k for kilo and m for megaG = 480VB = Prepared for batteries, battery drawers and cables

7、 included0 = No battery strings includedSKU Translation Guide跳转到第一页SKU Translation GuideSL 60 K FAPC SILCON SERIES60k = 60,000VAe.g. k for kilo and m for megaF = 200/208/220V跳转到第一页APC Service Bypass Panel SKU# ConfigurationExample: SBP20KHC3M1 - SBP40KHR2M1SBP shows that it is an APC Service Bypass

8、Panel40 shows the sizeK shows that the size is in kilowattH is 400VR2 means for two modules in N+1(redundancy)C3 means for three modules in N (full power)M1 means one main feeds the unit跳转到第一页SBP 60K H C 3 M1Service Bypass Panel60 kVA/kW400 V3 parallel unitsC: CapacityR: RedundancySingle MainsSKU Tr

9、anslation Guide跳转到第一页Silcon DP300E Principle DiagramMain componentsMain InverterLoadDelta InverterDeltaTransformer跳转到第一页Main InverterBatteryDelta InverterDeltaTransformerSilcon DP300E - power flow1. Normal, regulated operation2. Battery operation3 Battery rechargePerformancesRegulating the delta, di

10、ff. in/outRegulating the delta, diff. in/outRegulating Delta, diff. in/out跳转到第一页Power-Flow Analysis. nominal voltageVoltage 100%Current 100%Power 100%100%100%100%100%100%100%Main Inverter(0%)(0%)Delta InverterDeltaTransformer0%Performances跳转到第一页Power-Flow Analysis. -15% voltageVoltage 85%Current 115

11、%Power 100%100%115%115%100%100%100%15%15%15%Main InverterDelta InverterDeltaTransformerPerformances跳转到第一页Power-Flow Analysis. + 15% voltageVoltage 115%Current 85%Power 100%100%85%85%100%100%100%15%15%15%Main InverterDelta InverterDeltaTransformerPerformances跳转到第一页Power-Flow Analysis. battery chargin

12、g Voltage 100%Current 110%Power 110%100%110%110%100%100%100%10%0%10%Main InverterDelta InverterDeltaTransformer0%Performances跳转到第一页Main Inverter:4-Quadrant Pulse-Width Modulated Inverter Controls output voltage Charges batteries Supplies load during battery operation Delta Conversion On-line Main In

13、verterMain componentsMain InverterDelta InverterDeltaTransformer跳转到第一页Delta Conversion On-line Delta InverterDelta inverter:4-Quadrant Pulse-Width Modulated Inverter Controls input current Controls battery charging Makes up for any differences between in- and output voltage Regulates input power fac

14、tor Main componentsMain InverterDelta InverterDeltaTransformer跳转到第一页Delta Conversion On-lineBasic Configuration:Basic Configuration:4Q-PWM Inverter is capable of distributing energy in either forward or reverse direction, which means that theinverter can work as a charger as well.In the UPS we use f

15、ly-back diodes to pass energy to the batteries.VoutIoutHalf-bridge 4Q-inverterIoutVout3. Inverter1. Inverter2. Charger4. Charger4Q Pulse-Width Modulated InverterMain components跳转到第一页Delta Conversion On-line Forward mode / Inverter modeForward mode / Inverter mode Current flowing out of inverter Inve

16、rter building sinusoidal output voltage Switching of inverter controlled by control loop. Control loop senses output voltage and compares it to the reference. Any differences will make changes in the PWM switching signals to make corrections very quick. Main componentsPositive periodsNegative period

17、s跳转到第一页Delta Conversion On-lineReverse mode/ rectifier modeReverse mode / rectifier mode Current flowing in to inverter Inverter still building sinusoidal output voltage The switching of the inverter is controlled by the same control loop as in forward/inverter mode. The current is now flowing throu

18、gh the fly-back diodes to the batteries Main componentsPositive periodsNegative periods跳转到第一页Battery ChargingDelta Conversion On-lineBattery ChargingMain componentsMain InverterDelta InverterDeltaTransformerInput power 110%Output power 100% Battery Power 10%We cannot store energy in a pointDue to Ki

19、rchoff law, the energy willflow to the battery, as the energyhas to be in balance.Batteries are chargedby passing energy throughInverter fly-back diodes 跳转到第一页Main Inverter Constant voltage regulation Output voltage is kept to a reference Basically, it is a PI-regulation, where the actual value is c

20、ompared to a reference. The result is given to the controller, which will adjust the voltage. The constant voltage control results in a low internal impedance. 4 Q Pulse-Width Modulated InverterMain InverterPWMOutput voltage ref.Delta Conversion On-lineMain Inverter Main components跳转到第一页Delta Invert

21、er Constant Current RegulationThe Current is kept to a reference Basically it is a PI-regulation, where the actual value is compared to a reference. The result is given to the Controller, which is adjusting the Current. The reference is calculated according to the load and the charge level of the ba

22、tteriesThe constant current regulation results in a high internal impedance. 4 Q Pulse-Width Modulated InverterDelta InverterBatteryPWMBattery voltage ref.Input current ref.Delta Conversion On-lineDelta InverterMain componentsDelta InverterDeltaTransformer跳转到第一页Silcon ups 的电路组成的电路组成 1 1: Electronic

23、boardsElectronic boards Mains controllerMains controller psupsu communication boardcommunication board display boarddisplay board parallel boardparallel board system Integration interface boardsystem Integration interface board RFI FilterRFI Filter 2: 2: power modulepower module TSM mains inverter d

24、elta inverter SSWTSM mains inverter delta inverter SSW dc capacitordc capacitor ac capacitor and output chockac capacitor and output chock跳转到第一页 Mains controllerMains controller 4 4 cpucpu controlcontrol store log and store log and config config PSUPSU One dc source and two ac sourcesOne dc source a

25、nd two ac sources output 20v 12v 5v -12voutput 20v 12v 5v -12v on-off switchon-off switch reset reset 跳转到第一页 TSMTSM Mains Mains inverterinverter IGBT inverter and driver IGBT inverter and driver charge the batterycharge the battery control the output voltcontrol the output volt batt batt operationop

26、eration Delta Delta inverterinverter 1:5 1:5 transformertransformer control input currentcontrol input current driverdriver跳转到第一页Communication boardnDisplay controln2*232nsignal portnfiber link跳转到第一页 SSWSSW Its own power supplyIts own power supply transfertransfer one for mains ,one for one for main

27、s ,one for bypassbypass SCRSCR Crowbar Crowbar Charge Charge modulemodule Charge dc capacitor before Charge dc capacitor before batt batt connectionconnection protect dc capacitorprotect dc capacitor跳转到第一页跳转到第一页跳转到第一页Parallel board nShare load, synchronousnbypass operationnX021-X020none is master H1

28、nred parnstand by跳转到第一页DP310E - DP340E Parallel System with Service Bypass PanelMains SupplySBPDistribution PanelDP310E - DP340ELoadsDP310E - DP340E跳转到第一页Service Bypass Panel -SBP300EBy-pass panel for By-pass panel for efficient installation efficient installation and safe and safe maintenancemainte

29、nance Service By-pass panelService By-pass panelSwitch panel for service purpose operationIntelligent communication to Silcon DP300E eliminates fault operationSignal lamps indicate correct panel operation跳转到第一页SBP 连线图连线图跳转到第一页Fuse Box - MCCB BoxGuarding the Silcon DP300E external battery bankGuardin

30、g the Silcon DP300E external battery bankProtects against electric shocksEnhances safety with coiling and tripping facilitiesSafe battery Safe battery installationinstallation跳转到第一页MCCB跳转到第一页跳转到第一页Play time跳转到第一页SILCON的安装的安装跳转到第一页UPS系统示意图系统示意图 电网电网输出配电柜输出配电柜负载负载维修旁路开关维修旁路开关输入切换配电柜输入切换配电柜油机油机What is

31、a UPS ?SilconDP300E后备时间后备时间22小时小时跳转到第一页MCCB跳转到第一页PlaceingnEasy to servicenairflow at least 0.5mnno water tubenno direct sunlightnMCCB SBPnenough space for replace modulenhigh horizon 1500m跳转到第一页Central system and protective earth.Separate neutral andprotective earth wires.TN-S NetworkTN-S Network跳转到

32、第一页TN-C NetworkCentral system and protective earth.Combined neutral andprotective earth wires.TN-C Network跳转到第一页Relation between line to line voltage and neutral to line voltage is 3= 1.73 in3-phase networks.Use neutral to line voltage to find the phase currents for a given load !Example: Total load

33、 15 kVA (symmetrical)Line to line voltage 400VLoad per phase 15 / 3 = 5 kVANeutral to line voltage = 400 / 1.73 = 230VPhase current = 5000 / 230 = 21.74A Star connected loadsL1L2L3N400V230V400VThree phase LoadsFind the phase current.跳转到第一页connectionn1:cable n5A/mm 95mmn3 phase 5 line neutraln2: fann

34、3: phase order跳转到第一页跳转到第一页跳转到第一页跳转到第一页自制自制SBP 连线图连线图跳转到第一页 Volt might be here even if you sure itsVolt might be here even if you sure its notnot Metal thingsMetal things Cooperation with local electricianCooperation with local electrician Dont shutdown User loadDont shutdown User load,SBPSBP跳转到第一页Pa

35、rallel Operation- for expansion and redundancy or both.Expandable跳转到第一页Silcon DP300E UPSs in parallel connection.* Sharing the loadsSharing the loads The most direct The most direct connectionconnection Less stress on Less stress on componentscomponents跳转到第一页并机几种运行方式并机几种运行方式n1:冗于方式: N+1n2:并机方式:LOADN

36、+1n3:ADVANCE n4:BYPASSn5:BATTERY跳转到第一页Advanced power managementDay 1Day 2Day 3Optimized redundancy Optimized redundancy operation by control operation by control systemsystem- only the systems needed to supply the load will be “active”.- the load can be switched between the systems in a preprogrammed sequence.跳转到第一页BYPASSn1: No1 OPERATION BYPASS, TWO TRANSFER AT SAME TIMEn2:No 2 OPERATION BACK,nTWO BACK 。跳转到第一页BATTERY OPERATIONn1:MAINS FAULT n2:ONE MAINS FAULT nLOAD N+1nLOAD10%15%跳转到第一页BATTERY跳转到第一页通信通信跳转到第一页并机通信报警并机通信报警