1、In sulati on Mon itor for Ungroun ded DC Mai ns CM-IWN-DCSPDT Relay OutputDescriptionca Selector switch for open- or closed circuit principleb Response threshold 10110 kc U: green LED - supply voltage d L+: red LED - faulte L-: red LED - faultf Test button: Test - Resetg Test button: Test - L- Insul

2、ation resistance monitoring in ungrounded pure DC systems from 24 240 V DC Adjustable range 1011CD Selector switch for normally energized or de-energized operation Onboard and external test-reset feature SPDT contact 3 LEDs for status indicationTEDAccessories丸 |Pariel Mounting 、AdapterY 44Q C29 R 01

3、00Transparent Cover45.0 PNT45.0 iTvrnP/N;1SVR 440 005 H 01OCSee accessory pages for speci?cations.9.301TBCC01CJ09CC201The CM-IWN-DC is designed for insulation resistance monitoring in ungrounded, pure DC supply systems with or without ?ltering. Due to its electrical isolation between the supply circ

4、uit and the measuring circuit, it can be supplied either by an external auxiliary voltage or by the supply voltage to be monitored. Insulation resistance faults are evaluated separately for L+ or L- and displayed by LEDs. Due to its measuring principle, the CM-IWN-DC is not able to detect balanced e

5、arth-leakage faults. The response threshold is adjustable in a range from 10 to 110 k the insulation resistance falls below the set response threshold, the relay transfers and the error LED glows.Front-face test buttonFront-face test buttonConnection S2-S3:Q. IfTest L- ” :insulation fault can be sim

6、ulated, pressing the testbutton = output relay will trip (energized, de-energize)Tesj_ /ResetL+ ” : Press 1 s = Reset L+ and L-jumper = fault tripping is stored,button with n/o contact = remote reset, pressing the button resets storage of the tripped stateFunctionRemote memory, resetS3/S2In sulati o

7、n resista nceR 1,6xRxadjusted trip pointRx L+(L-)/Rx=A1/A2On board test butt onRemote test L-S3/S4Remote test L+S3/S1Normally de-e nergized|Normally energized i.Output relay15/1815/16tT test approx. 1 sApplication and Connection ExampleL+NLeaaov yyQQJSCDrcAVQZ -.41 y bB2L- L-十1G_l_I_1riA1i e md-Alt5

8、 SiS3SdlLi L-11 I1$R -厂严i!A1Ai11 I UL-ASConnectionA1-A2Supply voltageS1 to S4Con trol in putsS3-S1Remote test butt on L+S3-S4Remote test butt on L-S3-S2Remote test butt onstorage / resetL+,L-,丄Measuri ng circuit15-16/18 Output contactsOrdering TableSupply voltagePart Number24 240 V AC/DC1SVR 450 065

9、 R 0000Low Voltage Products & SystemsABB Inc Sales Information 1-8B8-3&5-1221I * Technical Assistance 1-800-377-SSAC (7722) 1BZCDN wIn sulatio n Mon itor for Ungroun ded DC Mains CM-IWN-DCSPDT Relay OutputLoad Limit CurvesInputSupply voltage - power consumptionTolerance of supply voltage24.24.A1-A2

10、.240 V AC .240 V DC24.240 V AC/DC - ? 5.5 VA / W-15 % . +10 % (50.60 Hz)-15 % . +10 %Measuring circuitMeasuring input Response valueL+, L-,占10.110 k QInternal resistance min.57 k QMeasuring voltage24.240 V DCIsolation voltage max.300 V DCCable length for test and reset switch10 mTime Delay 1 s at R

11、isolation 0.9 x response valueDisplay of Operational StatusSupply voltageLED, greenFault at L+LED, redFault at L-LED, redOutput15-16/18Relay, 1 SPDTRated voltageVDE0100,IEC 947-1400 VRated switching voltage max.400 V ACRated switching currentAC 12 (resistive)5 A (at 230 V)AC 15 (inductive)3 A (at 23

12、0 V)DC 12 (resistive)5 A (at 24 V)DC 13 (inductive)2.5 A (at 24 V)Maximum mechanical life30 x 10 6 operationsMaximum electrical life (acc. to AC 12 / 230 V / 5 A)1 x 105 operationsShort-circuit proof, max. fuse rating5 A / fast actingGeneral DataRated impulse withstand voltage Vimp4 kVOperating temp

13、erature range-25 C . +65 CStorage temperature range-40 C . +85 CMounting on DIN rail (EN 50022)Snap-on mounting/screw mounting with an adapterCable size stranded with wire end ferrule2 x 14 AWG (2 x 2.5 mm 2)WeightApprox. 0.66 lb (300 g)Technical DataAC Load (Resistive)R-ed:LK:ticin Factor few IndLKzlivB AC LoadGordract Ufe-tirreIWNDC2B112.22.04Low Voltage Products & Systems1TBCC01CJ09GC201Mechanical ViewInches (Mfilllimeten?)9.31ABB Inc Sales Information 1-888*-3S5-1221 Technical Assistance 1 -80i-a77-SSAC f7722)