1、【精品文档】如有侵权,请联系网站删除,仅供学习与交流自动喷水灭火系统末端试水装置放水试验工程名称湖南商会大厦消防系统工程建设单位湖南湘电房地产开发有限公司施工单位南京市消防工程有限公司设计单位湖南建筑设计院生产厂商/试验日期 2011年5月18日序号设置位置流量压力水流指示器动作时间压力开关动作时间水力警铃动作时间结论1负二层-10.95L/S0.052MPa90S90S90S正常2负二层-20.95L/S0.052MPa90S90S90S正常3负二层30.95L/S0.052MPa90S90S90S正常4负一层10.95L/S0.052MPa90S90S90S正常5负一层20.95L/S0.

2、052MPa90S90S90S正常6负一层30.95L/S0.052MPa90S90S90S正常7负一层40.95L/S0.052MPa90S90S90S正常8 一层0.95L/S0.052MPa90S90S90S正常9二层0.95L/S0.052MPa90S90S90S正常10三层10.95L/S0.052MPa90S90S90S正常11三层20.95L/S0.052MPa90S90S90S正常12四层10.95L/S0.052MPa90S90S90S正常13四层20.95L/S0.052MPa90S90S90S正常14东5层0.95L/S0.052MPa90S90S90S正常15东5层0.

3、95L/S0.052MPa90S90S90S正常16东6层0.95L/S0.052MPa90S90S90S正常17东7层0.95L/S0.052MPa90S90S90S正常18东8层0.95L/S0.052MPa90S90S90S正常19东9层0.95L/S0.052MPa90S90S90S正常20东10层0.95L/S0.052MPa90S90S90S正常21东11层0.95L/S0.052MPa90S90S90S正常22东12层0.95L/S0.052MPa90S90S90S正常23东13层0.95L/S0.052MPa90S90S90S正常24东14层0.95L/S0.052MPa90S

4、90S90S正常25东15层0.95L/S0.052MPa90S90S90S正常26东16层0.95L/S0.052MPa90S90S90S正常27东17层0.95L/S0.052MPa90S90S90S正常28东18层0.95L/S0.052MPa90S90S90S正常29东19层0.95L/S0.052MPa90S90S90S正常30东20层0.95L/S0.052MPa90S90S90S正常31东21层0.95L/S0.052MPa90S90S90S正常32东22层0.95L/S0.052MPa90S90S90S正常33东23层0.95L/S0.052MPa90S90S90S正常34东2

5、4层0.95L/S0.052MPa90S90S90S正常35东25层0.95L/S0.052MPa90S90S90S正常36东26层0.95L/S0.052MPa90S90S90S正常37东27层0.95L/S0.052MPa90S90S90S正常38东28层0.95L/S0.052MPa90S90S90S正常39西5层0.95L/S0.052MPa90S90S90S正常40西6层0.95L/S0.052MPa90S90S90S正常41西7层0.95L/S0.052MPa90S90S90S正常42西8层0.95L/S0.052MPa90S90S90S正常43西9层0.95L/S0.052MPa

6、90S90S90S正常44西10层0.95L/S0.052MPa90S90S90S正常45西11层0.95L/S0.052MPa90S90S90S正常46西12层0.95L/S0.052MPa90S90S90S正常47西13层0.95L/S0.052MPa90S90S90S正常48西14层0.95L/S0.052MPa90S90S90S正常49西15层0.95L/S0.052MPa90S90S90S正常50西16层0.95L/S0.052MPa90S90S90S正常51西17层0.95L/S0.052MPa90S90S90S正常52西18层0.95L/S0.052MPa90S90S90S正常5

7、3西19层0.95L/S0.052MPa90S90S90S正常54西20层0.95L/S0.052MPa90S90S90S正常55西21层0.95L/S0.052MPa90S90S90S正常56西22层0.95L/S0.052MPa90S90S90S正常57西23层0.95L/S0.052MPa90S90S90S正常58西24层0.95L/S0.052MPa90S90S90S正常59西25层0.95L/S0.052MPa90S90S90S正常60西26层0.95L/S0.052MPa90S90S90S正常61西27层0.95L/S0.052MPa90S90S90S正常62西28层0.95L/S0.052MPa90S90S90S正常试验经过及问题处理: 打开系统的末端试验阀,从末端试水装置放水,观察压力表上的压力值为 0.52MPa,此时压力开关、水流指示器动作报警,并启动喷淋泵,同时水力警铃发出报警信号。建设(监理)单位: 代表:技术负责人质检员施工员.精品文档. 自动喷水灭火系统末端试水装置放水试验 编号:B-23