2022年powerengineeringlecturesbg2steamheatingsystems动力工程英文教材教程教案讲义

上传人:高**** 文档编号:233972986 上传时间:2022-01-03 格式:DOCX 页数:5 大小:32.68KB
返回 下载 相关 举报
2022年powerengineeringlecturesbg2steamheatingsystems动力工程英文教材教程教案讲义_第1页
第1页 / 共5页
2022年powerengineeringlecturesbg2steamheatingsystems动力工程英文教材教程教案讲义_第2页
第2页 / 共5页
2022年powerengineeringlecturesbg2steamheatingsystems动力工程英文教材教程教案讲义_第3页
第3页 / 共5页
2022年powerengineeringlecturesbg2steamheatingsystems动力工程英文教材教程教案讲义_第4页
第4页 / 共5页
2022年powerengineeringlecturesbg2steamheatingsystems动力工程英文教材教程教案讲义_第5页
第5页 / 共5页
亲,该文档总共5页,全部预览完了,如果喜欢就下载吧!
资源描述

《2022年powerengineeringlecturesbg2steamheatingsystems动力工程英文教材教程教案讲义》由会员分享,可在线阅读,更多相关《2022年powerengineeringlecturesbg2steamheatingsystems动力工程英文教材教程教案讲义(5页珍藏版)》请在金锄头文库上搜索。

1、Power Engineering Lectures - BG2 Steam Heating Systems动力工程英文教材教程教案讲义Steam Heating Systems HVAC 6022 1 Learning Outcome When you complete this module you will be able to: Describe the operating principles and maintenance procedures of steam heating systems and the components of these systems. Learnin

2、g Objectives Here is what you will beable to do when you complete each objective: 1. Describe standard types of piping andequipmentlayoutforsteamheatingsystems.2.Describethegeneraloperationand maintenance of steam heating systems. 3. Apply a steam heating system trouble-shootingguide.INTRODUCTION Th

3、e piping and heating units of a steam heating system must be so arrangedthat:1.Steam can flowfreelyand insufficientquantitiesto allheatingunits. 2.The condensate can be removed freely from these units and returned to the boiler.3. The aircan be expelledfrom the heatingunitsand piping. Inallsystems t

4、he horizontalsteam supplypipes between boilerand heatingunitsare calledthe mains; the verticalpipes to the various floors, the risers. When the supply mains are located below the heating units they serveand the steam is supplied upwards through the risers to the heating units, the system iscalled an

5、 upfeed system. In a downfeed system, the mains are located above the heating units. The pipes carrying the condensate back to the condensate tank or boiler are called the return risers and return mains. When the return main of a gravity return system is located belowthe level of the water line in t

6、he boiler and, therefore always filled with water, it iscalled a wet return. On the other hand, a return main located above the water line, whichis usually only partly filled with condensate and will drain dry when the flow of condensate ceases, is called a dry return. Many types of steam heating sy

7、stems have been developed,each having advantages and disadvantages over the others. These systems are classifiedaccordingto pipingarrangement,operatingpressure,and method of returningcondensate to the boiler. In regard to classification by piping arrangement, the heating system may beeither the one

8、pipe or the two-pipe design. In terms of operating pressures, the system may be high pressure, low pressure, vapor, or vacuum. In regard to methods of returning condensate to the boiler, the system may use a gravity return, a return trap, a condensate return pump, or a vacuum pump. Some of these des

9、igns, such as the one pipe system, areobsolete and hence are no longer used in modern installations. However,they are described in order to help the student understand the principles involved in steam for heating buildings. HVAC 6022 2ONE PIPE, GRAVITY RETURN SYSTEM The one-pipe system, also called

10、the air vent system,was one of the first steam heating systemsto be developed. A singlemain is used tocarry both the steam supply from the boiler to the radiators and the steam condensate from theradiators back to the boiler. Each radiator has only a single connection and steam is fedfrom the main t

11、o the radiatorthrough thisconnection. Asthe steam in the radiatorcondenses, it drains by gravity back to the steam main through the single connection. The end of thesteam supply main is tied into the condensate return main. All piping is sloped downward so that the condensate can flow freely by grav

12、ity back to the boiler without interferingwith the flow of the steam. TWO-PIPE, GRAVITYRETURNSYSTEM Toovercome the difficulties可编辑资料 - - - 欢迎下载encountered when steam and condensate flow in opposite directions in the same pipe, the two-pipe steam heating system was developed. In this system, which op

13、erates at pressures between 0 - 103 kPa, gauge separate steam and condensate return mains are used. Eachradiator has two connections. The steam flows from the steam main through the radiator valve to the radiator. As the steam condenses, it flows out through another valve into the return main and ba

14、ck to the boiler. Air vents in the upper part of the radiator remove the air.This system, now obsolete, had the disadvantage that during start-up some steam could pass through a radiator without condensing and could enter other radiators via the return main, thus trapping the air in the center.TWO-P

15、IPE, RETURN TRAP SYSTEM In a gravity returnsystem, the boilershould be placed wellbelow the lowest radiatoror convectorin the heating system in order to obtain sufficient static head for the returning condensate to overcomethe boiler pressure. In buildings with low basement ceilings, it was sometime

16、s necessaryto set the boilerin a pitbelow the floorin orderto obtainthe requiredstatichead. This difficulty was overcome by the use of a return trap, which returns the condensate to theboiler. HVAC 6022 3 BG_2_0_2.jpg GFig. 1 shows a diagram of a return trap system while Fig. 2 shows a basic diagram of the return

展开阅读全文
相关资源
相关搜索

当前位置:首页 > 中学教育 > 高中教育

电脑版 |金锄头文库版权所有
经营许可证:蜀ICP备13022795号 | 川公网安备 51140202000112号