一、通风管道流量阻力表一、通风管道流量阻力表1、缩伸软管摩擦阻力表、缩伸软管摩擦阻力表圆形风管v=2 m/sv=3 m/sv=4 m/sv=5 m/sv=6 m/sΦ150127/0.43190/0.98254/1.8318/3.23381/4.46Φ200226/0.32339/0.73452/1.30565/2.03678/2.92Φ250353/0.26530/0.558707/1.04883/1.621060/2.33Φ300509/0.21764/0.951018/1.621273/2.441521/3.582、镀锌板风管摩擦阻力表、镀锌板风管摩擦阻力表风量(m3/h)/摩擦阻力(Pa)矩型风管mmv=2m/sv=3 m/sv=4 m/sv=5 m/sv=6 m/s120x120104/0.61156/1.27207/2.15259/3.25311/14.57160x120138/0.51207/1.07277/1.8346/2.75415/3.86160x160184/0.42277/0.78369/1.49461/2.26553/3.17200x120173/0.46259/0.95346/1.62432/2.45734/3.44200x160230/0.36346/0.77461/1.3576/1.79691/2.78250x120216/0.41324/0.87432/1.47540/2.23648/250x160288/0.32432/0.69576/1.17720/1.77864/2.48250x200360/0.27540/0.58720/0.99900/1.501080/2.11320x120269/0.38403/0.79537/1.34672/2.03806/2.86320x160369/0.29553/0.61737/1.04922/1.581106/2.22320x200461/0.25691/0.519221/0.871152/1.311382/1.85320x250576/0.21864/0.431152/0.741440/1.121728/1.57400x120336/0.35504/0.74673/1.25841/1.901009/2.67400x160461/0.27691/0.56922/0.951152/1.451382/2.03400x200576/0.22864/0.461152/0.781440/1.201728/1.68400x250720/0.191080/0.381440/0.661800/1.002160/1.40500x160576/ 0.25864/0.521152/0.891440/1.341728/1.89500x200720/0.211080/0.421440/0.731800/1.12160/1.54500x250900/0.171350/0.351800/0.602250/0.902700/1.28500x3201152/0.141728/0.282304/0.492880/0.753456/1.05500x4001440/0.122160/0.252880/0.423600/0.644320/0.89630x160726/0.221089/0.481452/0.841814/1.122177/1.98630x200907/0.191361/0.391814/0.672268/1.022722/1.43630x2501134/0.161701/0.322268/0.552835/0.833402/0.19630x3201452/0.132177/0.262903/0.443629/0.674355/0.94630x4001814/0.112722/0.223629/0.374536/0.565443/0.79630x5002268/0.13402/0.194536/0.315670/0.486804/0.68800x160922/0.201382/0.421843/0.672304/1.022765/2.15800x2001152/0.181728/0.372304/0.632880/0.953456/1.34800x2501440/0.142160/0.32880/0.513600/0.774320/1.08800x3201843/0.12765/0.233686/0.404608/0.605530/0.851000x2001440/0.162160/0.352880/0.603600/0.904320/1.301000x2501800/0.132700/0.283600/0.484500/0.725400/1.021000x3202304/0.113456/0.234608/0.375760/0.576912/0.80圆形风管v=2 m/sv=3 m/sv=4 m/sv=5 m/sv=6 m/sΦ10055/0.7683/1.58111/2.68139/4.05166/5.69Φ140109/0.49164/1.03219/1.75273/2.64328/3.72Φ200224/0.31336/0.66448/1.12560/1.69672/2.38Φ2503.49/0.24524/0.5698/0.85873/1.281048/1.80Φ360727/0.151090/0.321454/0.541817/0.822180/1.15Φ400898/0.131347/0.281796/0.472245/0.722694/1.01Φ5001405/0.12108/0.212811/0.363513/0.554216/0.77说明(1).软管采用荷兰数据时,上述数据乘以下系数:Φ150 x2; Φ200 x1.8; Φ250 x1.5; Φ300 x1.3(2).局部摩擦阻力:ΔP (Pa)散流器喉径(mm)v=2m/sv=3 m/sv=4 m/sv=5 m/sv=6m/s200x20015.935.763.499.1142.7300x30023.853.595.1148.7214.1400x40029.466.0117.3183.2263.9(3)与散流器的摩擦阻力:ΔP (Pa)接管规格(mm)v=2m/sv=3 m/sv=4 m/sv=5 m/sv=6m/s镀锌管 200x2002.45.39.414.721.2镀锌管 400x4006.414.3225.539.857.3软管 Φ15010.822.328.841.354.1软管 Φ35010.122.740.463.190.8(4).保持风速必须的动压:当 v=2m/s 时, ΔP=2.4Pa; 当 v=3m/s 时, ΔP=5.4Pa当 v=4m/s 时, ΔP=9.6Pa; 当 v=5m/s 时, ΔP=15Pa当 v=6m/s 时, ΔP=21PaV2(5).其他局部阻力的计算按下式: 2gΔP=ζ─γ二、室内送回风口尺寸表二、室内送回风口尺寸表1、风口风量冷量对应表、风口风量冷量对应表冷量RTkw风量m/h送风口mm回风口mm1.03.5750700x150800x1501.55.3800700x150800x1502.071000900x1501000x150/800x2002.58.714501000x2001200x2003.010.516001100x2001300x2003.512.218001250x200/1000x2501500x200/1200x2504.01419501000x2501300x2505.017.583000 1600x250/1360x3002、不同送风方式的风量指标和室内平均流速、不同送风方式的风量指标和室内平均流速 ASHRAE送风方式单位地板面积的送风量 l/sm2工作区平均流速 m/s换气次数 h-1侧送百叶风口条形风口局部孔板送风顶棚散流器顶棚孔板送风3--64--105--155--255-500.13--0.180.10--0.180.10--0.180.10--0.250.05--0.15712183060三、室内风管风速选择表三、室内风管风速选择表1、低速风管系统的推荐和最大流速、低速风管系统的推荐和最大流速 m/s住宅公共建筑工厂 应用场所 推荐最大推荐最大推荐最大室外空气入口空气过滤器加热排管冷却排管淋水室风机出口主风管支风管(水平)2.51.32.32.32.56.04.03.04.01.52.52.32.58.56.05.02.51.52.52.52.59.06.04.04.51.83.02.52.511.08.06.52.51.83.03.02.510.09.05.08.01.83.53.02.514.011.09.0支风管(垂直)2.54.03.56.04.08.02、低速风管系统的最大允许速、低速风管系统的最大允许速 m/s以摩擦阻力控制 应用场所以噪声控制主风管送风主管回风主管送风支管回风支管住宅公寓、饭店房间办公室、图书馆大礼堂、戏院银行、高级餐厅百货店、自助餐厅工厂3.05.06.04.07.59.012.55.07.510.06.510.012.015.04.06.57.55.57.57.59.03.06.08.05.08.08.011.03.05.06.14.06.06.07.53、通风系统之流速、通风系统之流速 m/s系统商业工业低 速送风、最大流速送风、一般流速回风、最大流速回风、一般流速136--11107.5--91311--13139--13高速、一般1313--25室内允许噪声dB(A)主管风速m/s支管风速m/s25-353-4≤235-504-62-3注:民用住宅≤35dB(A),商务办公≤45dB(A)。
四、室内风口风速选择表四、室内风口风速选择表1、送风口风速、送风口风速卧 室 1.5-2m/s (风口在上部时)起 居 2-3m/s (风口在上部时)3m/s (风口距地≤2.5m) 办 公 室4m/s (风口距地≤4.5m)商场、娱乐 3-5m/s2、以噪音标准控制的允许送风流速、以噪音标准控制的允许送风流速 m/s应用场所流速 m/s图书馆、广播室住宅、公寓、私人办公室、医院房间银行、戏院、教室、一般办公室、商店、餐厅工厂、百货公司、厨房1.75--2.52.5--4.04.0--5.05.0--7.53、推荐的送风口流速、推荐的送风口流速 m/s应用场所流速 m/s播音室戏院住宅、公寓、饭店房间、教室一般办公室电影院百货店、上层百货店、地下1.5--2.52.5--3.52.5--3.82.5--4.05.0--6.05.07.510.04、送风口之最大允许流速、送风口之最大允许流速 m/s应用场所盘形送风口顶棚送风口侧送风口广播室医院疗房饭店房间、会客室百货公司、剧场教室、图书馆、办公室3.0--3.54.0--4.54.0--4.56.0--7.55.0--6.04.0--4.54.5--5.05.0--6.06.2--7.56.0--7.52.52.5--3.02.5--4.05.0--7.03.5--4.55、回风口风速、回风口风速房间净高风口位置风速3.5-4上部3-4m/s3-3.5上部2-3m/s2.5-3上部1.5-2m/s人不常停留处下部3m/s人常停留处下部1.5-2m/s走廊回风下部1-1.5m/s6、回风格栅的推荐流速、回风格栅的推荐流速 m/s位置近座位逗留区以上门下部门上部工业用流速 m/s2--33--443≥47、百叶窗的推荐流速、百叶窗的推荐流速 m/s位置新风回风减温器正面减温器旁通加热器旁通流速 m/s2.5--44--62--47.5--125--7.58、逗留区。