1、英文文献附录1:外文资料翻译A1.2原文TRANSFORMER1. INTRODUCTIONThe high-voltage transmission was need for the case electrical power is to be provided at considerable distance from a generating station. At some point this high voltage must be reduced, because ultimately is must supply a load. The transformer makes it

2、 possible for various parts of a power system to operate at different voltage levels. In this paper we discuss power transformer principles and applications.2. TOW-WINDING TRANSFORMERSA transformer in its simplest form consists of two stationary coils coupled by a mutual magnetic flux. The coils are

3、 said to be mutually coupled because they link a common flux.In power applications, laminated steel core transformers (to which this paper is restricted) are used. Transformers are efficient because the rotational losses normally associated with rotating machine are absent, so relatively little powe

4、r is lost when transforming power from one voltage level to another. Typical efficiencies are in the range 92 to 99%, the higher values applying to the larger power transformers.The current flowing in the coil connected to the ac source is called the primary winding or simply the primary. It sets up

5、 the flux in the core, which varies periodically both in magnitude and direction. The flux links the second coil, called the secondary winding or simply secondary. The flux is changing; therefore, it induces a voltage in the secondary by electromagnetic induction in accordance with Lenzs law. Thus t

6、he primary receives its power from the source while the secondary supplies this power to the load. This action is known as transformer action.3. TRANSFORMER PRINCIPLESWhen a sinusoidal voltage Vp is applied to the primary with the secondary open-circuited, there will be no energy transfer. The impre

7、ssed voltage causes a small current I to flow in the primary winding. This no-load current has two functions: (1) it produces the magnetic flux in the core, which varies sinusoidally between zero and m, where m is the maximum value of the core flux; and (2) it provides a component to account for the

8、 hysteresis and eddy current losses in the core. There combined losses are normally referred to as the core losses.The no-load current I is usually few percent of the rated full-load current of the transformer (about 2 to 5%). Since at no-load the primary winding acts as a large reactance due to the

9、 iron core, the no-load current will lag the primary voltage by nearly 90. It is readily seen that the current component Im= I0sin0, called the magnetizing current, is 90 in phase behind the primary voltage VP. It is this component that sets up the flux in the core; is therefore in phase with Im.The

10、 second component, Ie=I0sin0, is in phase with the primary voltage. It is the current component that supplies the core losses. The phasor sum of these two components represents the no-load current, orI0 = Im+ IeIt should be noted that the no-load current is distortes and nonsinusoidal. This is the r

11、esult of the nonlinear behavior of the core material.If it is assumed that there are no other losses in the transformer, the induced voltage In the primary, Ep and that in the secondary, Es can be shown. Since the magnetic flux set up by the primary winding,there will be an induced EMF E in the seco

12、ndary winding in accordance with Faradays law, namely, E=N/t. This same flux also links the primary itself, inducing in it an EMF, Ep. As discussed earlier, the induced voltage must lag the flux by 90, therefore, they are 180 out of phase with the applied voltage. Since no current flows in the secon

13、dary winding, Es=Vs. The no-load primary current I0 is small, a few percent of full-load current. Thus the voltage in the primary is small and Vp is nearly equal to Ep. The primary voltage and the resulting flux are sinusoidal; thus the induced quantities Ep and Es vary as a sine function. The avera

14、ge value of the induced voltage given byEavg = turnswhich is Faradays law applied to a finite time interval. It follows thatEavg = N = 4fNmwhich N is the number of turns on the winding. Form ac circuit theory, the effective or root-mean-square (rms) voltage for a sine wave is 1.11 times the average

15、voltage; thusE = 4.44fNmSince the same flux links with the primary and secondary windings, the voltage per turn in each winding is the same. HenceEp = 4.44fNpmandEs = 4.44fNsmwhere Ep and Es are the number of turn on the primary and secondary windings, respectively. The ratio of primary to secondary

16、 induced voltage is called the transformation ratio. Denoting this ratio by a, it is seen thata = = Assume that the output power of a transformer equals its input power, not a bad sumption in practice considering the high efficiencies. What we really are saying is that we are dealing with an ideal transformer; that is, it has no losses. Thus

展开阅读全文