1、 DSP-4000 Series Database Version 5.14 (Copper Tests), May 2004 Page 1 of 11 TIA CAT 6 Perm. Link Imped. Wire Map Res. length Delay Skew Prop. Delay Freq next attn RL* acr elfext PS next PS acr PS elfext Cable Type nvp limit Required Max nS nS MHz dB dB dB dB dB dB dB dB UTP 100 Cat 6 ScTP 100 Cat 6
2、 69 74 NA 12345678S | 12345678 12345678S | 12345678S N/A 90m 295ft 44 498 1.0 4.0 8.0 10.0 16.0 20.0 25.0 31.25 62.5 100.0 125.0 200.0 250.0 65.0 64.1 59.4 57.8 54.6 53.1 51.5 50.0 45.1 41.8 40.3 36.9 35.3 3.0 3.5 5.0 5.6 7.0 7.9 8.9 10.0 14.4 18.6 21.0 27.4 31.1 19.0 21.0 21.0 21.0 20.0 19.5 19.0 1
3、8.5 16.0 14.0 13.0 11.0 10.0 62.1 60.6 54.4 52.3 47.6 45.2 42.7 40.0 30.8 23.4 19.4 9.9 4.6 64.2 52.2 46.1 44.2 40.1 38.2 36.2 34.3 28.3 24.2 22.2 18.2 16.2 62.0 61.8 57.0 55.5 52.2 50.7 49.1 47.5 42.7 39.3 37.7 34.3 32.7 59.0 58.3 52.1 49.9 45.2 42.8 40.2 37.6 28.3 20.8 16.8 7.2 2.0 61.2 49.2 43.1
4、41.2 37.1 35.2 33.2 31.3 25.3 21.2 19.3 15.2 13.2 NOTE: All limits derived from the TIA/EIA-568-B.2.1 (Approved June 2002). * When attenuation is greater than 3 dB TIA CAT 5e Perm Link Imped. Wire Map Res. length Delay Skew Prop. Delay Freq next attn RL* acr elfext PS next PS acr PS elfext Cable Typ
5、e nvp limit Required Max nS nS MHz dB dB dB dB dB dB dB dB UTP 100 Cat 5e ScTP 100 Cat 5e 69 69 NA 12345678S | 12345678 12345678S | 12345678S N/A 90m 295ft 45 498 1.0 4.0 8.0 10.0 16.0 20.0 25.0 31.25 62.5 100.0 60.0 54.8 50.0 48.5 45.2 43.7 42.1 40.5 35.7 32.3 3.0 3.9 5.7 6.2 7.9 8.9 10.0 11.2 16.2
6、 21.0 19.0 19.0 19.0 19.0 19.0 19.0 18.0 17.1 14.1 12.0 57.0 50.9 44.5 42.3 37.3 34.8 32.1 29.3 19.4 11.3 58.6 46.6 40.6 38.6 34.5 32.6 30.7 28.7 22.7 18.6 57.0 51.8 47.0 45.5 42.2 40.7 39.1 37.5 32.7 29.3 54.9 47.9 41.5 39.3 34.3 31.8 29.1 26.3 16.4 8.3 55.6 43.6 37.6 35.6 31.5 29.6 27.7 25.7 19.7
7、15.6 NOTE: All limits derived from TIA/EIA-568B specifications. * When attenuation is greater than 3 dB TIA CAT6 Channel Imped. Wire Map Res. length Delay Skew Prop. Delay Freq next attn RL* acr elfext PS next PS acr PS elfext Cable Type nvp limit Required Max nS nS MHz dB dB dB dB dB dB dB dB UTP 1
8、00 Cat 6 ScTP 100 Cat6 69 74 NA 12345678S | 12345678 12345678S | 12345678S N/A 100m 328ft 50 555 1.0 4.0 8.0 10.0 16.0 20.0 25.0 31.25 62.5 100.0 125.0 200.0 250.0 65.0 63.0 58.2 56.6 53.2 51.6 50.0 48.4 43.4 39.9 38.3 34.8 33.1 3.0 4.0 5.6 6.3 8.0 9.0 10.1 11.4 16.5 21.3 24.6 31.5 36.0 19.0 19.0 19
9、.0 19.0 19.0 17.5 17.0 16.5 14.0 12.0 11.0 9.0 8.0 62.0 59.0 52.5 50.2 45.2 42.6 39.9 37.0 26.9 18.6 14.2 3.2 -2.8 63.3 51.2 45.2 43.2 39.2 37.2 35.3 33.3 27.3 23.2 21.3 17.2 15.3 62.0 60.5 55.6 54.0 50.6 49.0 47.4 45.7 40.6 37.1 35.4 31.9 30.2 59.0 56.5 49.9 47.7 42.5 39.9 37.2 34.3 24.1 15.8 11.3
10、0.3 -5.8 60.3 48.2 42.2 40.3 36.2 34.2 32.3 30.4 24.3 20.3 18.3 14.2 12.3 NOTE: All limits derived from the TIA/EIA-568-B.2.1 (Approved June 2002). * When attenuation is greater than 3 dB TIA CAT 5e Channel Imped. Wire Map Res. length Delay Skew Prop. Delay Freq next attn RL* acr elfext PS next PS a
11、cr PS elfext Cable Type nvp Limit Required Max nS nS MHz dB dB dB dB dB dB dB dB UTP 100 Cat 5 ScTP 100 Cat 5e 69 69 NA 12345678S | 12345678 12345678S | 12345678S N/A 100m 328ft 50 555 1.0 4.0 8.0 10.0 16.0 20.0 25.0 31.25 62.5 100.0 60.0 53.6 48.6 47.0 43.6 42.0 40.4 38.7 33.6 30.1 3.0 4.5 6.3 7.1
12、9.1 10.2 11.4 12.9 18.6 24.0 17.0 17.0 17.0 17.0 17.0 17.0 16.0 15.1 12.1 10.0 57.0 49.1 42.3 39.9 34.5 31.8 28.9 25.9 15.0 6.1 57.4 45.3 39.3 37.4 33.3 31.4 29.4 27.5 21.5 17.4 57.0 50.6 45.6 44.0 40.6 39.0 37.4 35.7 30.6 27.1 54.0 46.1 39.3 36.9 31.5 28.8 25.9 22.9 12.0 3.1 54.4 42.4 36.3 34.4 30.
13、3 28.4 26.4 24.5 18.5 14.4 NOTE: All limits derived from TIA/EIA-568-A addendum #5 and TIA/EIA 568-B. There were no changes in requirements for the Channel between addendum 5 and 568-B. * When attenuation is greater than 3 dB DSP-4000 Series Database Version 5.14 (Copper Tests), May 2004 Page 2 of 1
14、1 TIA CAT 6 BL (1999) Imped. Wire Map Res. length Delay Skew Prop. Delay Freq next attn RL* acr elfext PS next PS acr PS elfext Cable Type nvp limit Required Max nS nS MHz dB dB dB dB dB dB dB dB UTP 100 Cat 6 ScTP 100 Cat 6 69 74 NA 12345678S | 12345678 12345678S | 12345678S N/A 94m 308ft 45 518 1.
15、0 4.0 8.0 10.0 16.0 20.0 25.0 31.25 62.5 100.0 125.0 200.0 250.0 65.0 64.1 59.4 57.8 54.6 53.1 51.5 50.0 45.2 41.9 40.3 36.9 35.4 3.0 3.7 5.2 5.8 7.3 8.2 9.2 10.4 14.9 19.2 21.7 28.1 31.8 19.0 19.0 19.0 19.0 19.0 19.0 18.3 17.6 15.5 14.1 13.4 12.0 11.3 63.0 60.4 54.2 52.1 47.3 44.9 42.3 39.6 30.2 22
16、.7 18.6 8.9 3.5 63.1 53.2 47.1 45.2 41.1 39.2 37.2 35.3 29.3 25.2 23.3 19.2 17.2 62.0 61.8 57.0 55.5 52.2 50.7 49.1 47.6 42.7 39.3 37.7 34.3 32.7 60.0 58.1 51.9 49.7 44.9 42.5 39.9 37.2 27.7 20.1 16.0 6.3 0.9 60.1 50.2 44.1 42.2 38.1 36.2 34.2 32.3 26.3 22.2 20.3 16.2 14.2 NOTE: All limits derived from the ANSI/TIA/EIA Category 6 draft 5, May 1999 specifications. (This is an old draft. It re