1、X20IF1072 Data sheet V 2.201 X20IF1072 1 General information The X20IF1072 interface module can be used to expand the X20 CPU for specific applications. It is equipped with a CAN bus interface. CAN bus connection Integrated terminating resistor 2 Order data Model numberShort descriptionFigure X20 in

2、terface module communication X20IF1072X20 interface module, 1 CAN interface, max. 1 Mbit/s, electri- cally isolated, order 1x TB2105 terminal block separately. Required accessories Terminal blocks 0TB2105.9010Accessory terminal block, 5-pin, screw clamp 2.5 mm 0TB2105.9110Accessory terminal block, 5

3、-pin, cage clamp 2.5 mm Table 1: X20IF1072 - Order data X20IF1072 2Data sheet V 2.20 3 Technical data Product IDX20IF1072 Short description Communication module1x CAN bus General information B&R ID code0x1F20 Status indicatorsModule status, data transfer, terminating resistor Diagnostics Module stat

4、usYes, using status LED Data transferYes, using status LED Terminating resistorYes, using status LED Power consumption0.79 W Additional power dissipation caused by the actua- tors (resistive) W - Electrical isolation PLC - IF1Yes Certification CEYes UL 508 (cULus)LISTED 14F2 BR CSA HazLoc Cl I Div 2

5、 (cCSAus)ABCD T5 0-60C IP20 BR ATEX Zone 2 (EX)II 3G nA nC T5 0-60C IP20 BR KC (KC)Yes GL (GL)Yes GOST-RYes Interfaces IF1 interface SignalCAN bus 1) Design5-pin male multipoint connector Max. distance1000 m Transfer rateMax. 1 Mbit/s Terminating resistorsIntegrated in the module ControllerSJA 1000

6、Operating conditions Mounting orientation HorizontalYes VerticalYes Installation at elevations above sea level 0 to 2000 mNo limitations 2000 mReduction of ambient temperature by 0.5C per 100 m EN 60529 protectionIP20 Environmental conditions Temperature Operation Horizontal installation-25 to 60C V

7、ertical installation-25 to 50C Derating- Storage-40 to 85C Transport-40 to 85C Relative humidity Operation5 to 95%, non-condensing Storage5 to 95%, non-condensing Transport5 to 95%, non-condensing Mechanical characteristics NoteOrder 1x TB2105 terminal block separately SlotIn X20 CPU Table 2: X20IF1

8、072 - Technical data 1)This CAN bus interface can be configured as a CANopen master in Automation Studio 3.0 and higher. X20IF1072 Data sheet V 2.203 4 LED status indicators FigureLEDColorStatusDescription GreenOnInterface module activeSTATUS RedOnCPU starting up TxDYellowOnThe module is sending dat

9、a via the CAN bus interface TERMYellowOnTerminating resistor integrated in the module switched on Table 3: LED status indicators 5 Operating and connection elements LED status indicators IF1 - CAN bus Node number switches Terminating resistor switch on the bottom of the module Figure 1: Operating an

10、d connection elements 6 Node number switch Figure 2: Number switches for node numbers and transfer rates The node number for the interface is set with the two hex switches. X20IF1072 4Data sheet V 2.20 7 CAN bus interface The interface is a 5-pin multipoint plug. The 0TB2105 terminal block must be o

11、rdered separately. InterfacePinout TerminalFunction 1CANCAN ground 2CAN_LCAN low 3SHLDShield 4CAN_HCAN high 5NC 1 5 5-pin male multipoint connector Table 4: Pinout 8 Terminating resistor OnOff Terminating resistor switch Figure 3: Terminating resistor A terminating resistor is integrated in the inte

12、rface module. It can be turned on and off with a switch on the bottom of the housing. An active terminating resistor is indicated by the “TERM“ LED. 9 Firmware This module comes with preinstalled firmware. The firmware is a component of Automation Studio. The module is automatically updated to this version. To update the firmware included in Automation Studio, the hardware must be upgraded (see “Project manage- ment“ / “Automation Studio upgrade“ in the help system).

展开阅读全文