1、Gateway for XIP - Unitelway Schneider PLCRev 1.21 of 29Technical note n15Revision1.2 Last Update2004-05-11 DeviceW330Gateway for XIP - Unitelway Schneider PLC1 PurposeThis application note describes how to set up a remote collaboration. A remote collaboration consists in configuring, programming or

2、monitoring a PLC from a remote location, without the need of connecting directly the PC to the PLC. A remote collaboration therefore involves a TCP/IP connection and eventually a router, depending on the protocol used by the PLC. In this document, well configure a complete remote collaboration syste

3、m with a TSX Premium; the PL7 Pro software and, of course, an W330 as a router. The TSX Premium uses the Unitelway protocol. Three cases of remote collaboration will be treated: A direct connection to the W330 by Ethernet. A direct connection to the W330 using a phone line. With this topology, the W

4、330 IP address is known since it is established with your own PC at the PPP connection time. A connection to the W330 using Internet and callback. This kind of connection can be used with callback: we call the W330 and let ring a certain amount of time and we hang up. After a specified amount of tim

5、e, the W330 connects to the an ISP using its phone line. In this case, the W330 IP address is not known so that the W330 must publish its address, by mail for instance. This document will start with the first topology, then, when this configuration is running, the changes needed for the second one w

6、ill be described.The following graph shows the three network topologies.Figure 1: Network TopologiesThis document describes the three topologies. A direct Ethernet connection will be used to describe the global setup. After this configuration is working, the changes for the phone and Internet topolo

7、gies will be described elementsGateway for XIP - Unitelway Schneider PLCRev 1.22 of 29Gateway for XIP - Unitelway Schneider PLCTechnical note n15In order to follow this application note, you need: An W330 with an PSTN or ISDN modem and a firmware release that supports Unitelway ( = 3.5). A modem con

8、nected to your PC for direct phone connection with the W330 An Internet connection account both for your PC and for the W330. A TSX Premium or TSX Micro A TSX CX 100 cable from Schneider1 A cable to directly connect the PLC to the PC like the TSXPCX 1031 PL7 (in this document, PL7 PRO V4.4 is used)I

9、n this document, we use Windows XP but any operating system supported by PL7 Pro can be used. We also assume the reader has some knowledge of the PL7 software.1 Be careful that the D(B) signal corresponds to the A signal on the W330 and the D(A) corresponds to the B of theW330.Gateway for XIP - Unit

10、elway Schneider PLCRev 1.23 of 29Gateway for XIP - Unitelway Schneider PLCTechnical note n152 Configuration Steps OverviewStarting with an W330 out of the box, this document will show how to set up a remote collaboration using several steps. The purpose of some of the steps is to test what has been

11、set up so far. Those steps are therefore not absolutely necessary but can be really useful to localize a potential problem. The stets are: Setting up a test program in the PLC using a direct Unitelway connection PC ? ? PLC W330 Unitelway configuration Set up a tag to test the Unitelway configuration

12、 Configuring the W330 for XIP usage Installing and configuring the XIP driver Using the Remote CollaborationAfter each steps, a small test will be described to check the step has been executed correctly.Gateway for XIP - Unitelway Schneider PLCRev 1.24 of 29Gateway for XIP - Unitelway Schneider PLCT

13、echnical note n153 PLC ConfigurationWe will put a small program in the PLC so that we will be able to test the connection between the W330 and the PLC in the next section. To first set up the PLC, we will need a direct connection between the computer and the PLC. To do this, connect the PLC terminal

14、 port to the PC serial port (cable TSXPCX 1031 for instance). Once this is done, open PL7 PRO.3.1 PLC Test programPLC ? ConnectThe information is downloaded from the PLC to the PC and a screen looking like this appears.Figure 2: PL7 PROIf you already have a program installed in the PLC, save it. The

15、 program we will create contains a simple counter. We will use Ladder to build it.Gateway for XIP - Unitelway Schneider PLCRev 1.25 of 29Gateway for XIP - Unitelway Schneider PLCTechnical note n15Create the following program as a master sectionFigure 3: Test Program (Ladder)Confirm the program, disc

16、onnect from the PLC and reconnect. Transfer the program from the PC to the PLC and start the PLC.%S6%M100%M100 rising edgeINC %MW0Gateway for XIP - Unitelway Schneider PLCRev 1.26 of 29Gateway for XIP - Unitelway Schneider PLCTechnical note n154 W330 ConfigurationIn this section, we will show how to configure the W330 to access the PLC registers through an Unitelway configuration. The forwarding will be treated later.4.1 Setting the W330 IP AddressThe W330 is configured