1、Page 1BW-CS-11 (4/07)R10Motor Vessel (32 Bar LPSG) Control and Dosage Chart AGK 100 Boiler and Feedwater Treatment supplemented with AMERZINE Corrosion InhibitorRead MSDS before running these tests. Before testing, samples must be cooled to 25O C (77O F) by collecting through a sample cooler for saf

2、ety and to prevent flashing which concentrates the sample. If the sample is colored or turbid, filter before testing. If the sample remains cloudy after the first filtering, the sample should be refiltered through the same filter paper since the filter becomes more retentive on the second filtration

3、.MEANS OF ADJUSTMENTHYDRATE ALKALINITYUp to 700 S/cmS/cmS/cmS/cmS/cm - Satisfactory NORMAL MAINTENANCE BLOWDOWNAbove 700 S/cmS/cmS/cmS/cmS/cm INCREASE BLOWDOWN FREQUENCYBLOWDOWNBlowdown should be carried out as per boiler manufacturers instructions. Blowdown is necessary to reduce dissolved and susp

4、ended solids. If suspended solids are noticed in boiler water samples, blowdown regardless of conductivity test results. Weekly flash bottom blowdown for 10-20 seconds duration is advisable to remove normal sludge and to ensure clear operational lines.NEUTRALIZED CONDUCTIVITY3DREWSM Technical Servic

5、e112-ml1. Rinse and fill the plastic titration vial to the line (12-ml) with the cooled boiler water sample (Figure 1). 2. Pipette 2-ml of Barium Chloride 10% into the vial and swirl to mix (Figure 2). 3. Add 2 drops of Phenolphthalein Indicator and swirl. IF THE SAMPLE DOES NOT TURN PINK, the Hydra

6、te Alkalinity level is zero. Record zero on the Onboard Graphing Log and adjust dosage to increase hydrate alkalinity. IF THE SAMPLE TURNS PINK, counting the drops, add Sulfuric Acid N/10 until the sample is colorless (disregard the eventual reappearance of a pink color). Swirl the vial between drop

7、s (Figure 3). 4. Calculate the Hydrate Alkalinity concentration as follows: Number of drops of Sulfuric Acid N/10 x 5 = ppm Hydrate Alkalinity as OH. 5. Record the result and adjust dosage as necessary.2TEST RESULTS DOSAGE ADJUSTMENT1. Fill the sample cup to the 25-ml mark with cooled boiler water s

8、ample (Figure 1 & 2). 2. Place the AMERZINE corrosion inhibitor ampoules tapered tip into one of the four depressions in the bottom of the sample cup. Snap the tip by squeezing the ampoule toward the side of the cup. The sample will fill the ampoule and begin to mix with the reagent (Figure 1 & 2).

9、3. Remove the AMERZINE corrosion inhibitor ampoule from the cup. Mix the contents of the ampoule by inverting it several times, allowing the bubble to travel from end to end each time (Figure 3). 4. Wipe all liquid from the exterior of the ampoule and WAIT EXACTLY 10 MINUTES for full color developme

10、nt (Figure 4). 5. Place the AMERZINE corrosion inhibitor ampoule, flat end downward into the center tube of the comparator. Direct the comparator toward a source of bright white light while viewing from the bottom. Hold the comparator in a nearly horizontal position and rotate it until the color sta

11、ndard below the AMERZINE corrosion inhibitor ampoule shows the closest match (Figure 5). 6. Record the result and adjust dosage as necessary.1 & 2DAILY CONTROL TESTS10:00453TEST PROCEDUREIF LESS THAN 0.03 PPM supplement AGK100 treatment with AMERZINE corrosion inhibitorAMERZINE corrosion inhibitorDO

12、SAGE INFORMATIONFeed continuously as necessary with AGK 100 boiler and feedwater treatment.NOTE: Supplemental dosage is only necessary when the hydrazine level is not maintained by AGK 100 treatment alone.AGK 100 boiler and feedwater treatmentIF LESS THAN 40 PPM increase dosage by 25%40-65 PPM No do

13、sage adjustment necessaryIF GREATER THAN 65 PPM decrease dosage by 25%Initial dosage* is 2.5-5 liters/ton of boiler water in the system. Feed continuously with AMERZINE corrosion inhibitor.*When starting up a new system or one that has been down for some reason.HYDRAZINE1. Connect the Conductivity E

14、lectrode-ATC to the meter. Press the power button to power up the meter. 2. Add 2 drops of phenolphthalein indicator to the cooled boiler water sample and stir. If the sample turns pink, add Gallic Acid while stirring until the pink color disappears. This neutralizes the sample (Figure 2). 3. Place

15、the electrode into the sample and take care to ensure that the liquid level is above its upper steel band. Stir the electrode gently in the sample to create a homogenous sample (Figure 3). 4. Allow time for the reading to stabilize. Note the reading on the display. 5. Record the result and refer to

16、chart at right for blowdown adjustment.232003, 2007 Ashland Registered trademark, TM Trademark Ashland 1Registered trademark of CHEMetrics, Inc. Printed in U.S.A.Page 2APPARATUS Storage:Water Treatment Test Cabinet: PCN 1AA0016 (220 Volt) or 1AA2148 (110 Volt) Hydrazine:AMERZINE corrosion inhibitor Ampoule Test Kit: PCN 0369-01-8 includes: 1 Cylindrical Comparator, 1 Snap Cup, 1 Set of Instructions, 30 Ampoules Hydrate Alkalinity:Hydrate Alkalinity Test Kit: PCN 0388-01-8 includes: