1、 TD_SX460.GB_05.03_02 SX460 AUTOMATIC VOLTAGE REGULATOR (AVR) SPECIFICATION, INSTALLATION AND ADJUSTMENTS General description Technical specification SX460 is a half-wave phase-controlled thyristor type Automatic Voltage Regulator (AVR) and forms part of the excitation system for a brush-less genera

2、tor. In addition to regulating the generator voltage, the AVR circuitry includes under-speed and sensing loss protection features. Excitation power is derived directly from the generator terminals. Positive voltage build up from residual levels is ensured by the use of efficient semiconductors in th

3、e power circuitry of the AVR. The AVR is linked with the main stator windings and the exciter field windings to provide closed loop control of the output voltage with load regulation of +/- 1.5%. In addition to being powered from the main stator, the AVR also derives a sample voltage from the output

4、 windings for voltage control purposes. In response to this sample voltage, the AVR controls the power fed to the exciter field, and hence the main field, to maintain the machine output voltage within the specified limits, compensating for load, speed, temperature and power factor of the generator.

5、A frequency measuring circuit continually monitors the generator output and provides output under-speed protection of the excitation system, by reducing the output voltage proportionally with speed below a pre-settable threshold. A manual adjustment is provided for factory setting of the under frequ

6、ency roll off point, (UFRO). This can easily be changed to 50 or 60 Hz in the field by push- on link selection. Provision is made for the connection of a remote voltage trimmer, allowing the user fine control of the generators output. INPUT Voltage Jumper selectable 95-132V ac or 190-264V ac Frequen

7、cy 50-60 Hz nominal Phase 1 OUTPUT Voltage max 90V dc at 207V ac input Current continuous 4 A dc Intermittent 6 A for 10 secs Resistance 15 ohms minimum REGULATION +/- 1.5% (see note 1) THERMAL DRIFT 0.05% per deg. C change in AVR ambient (note 2) TYPICAL SYSTEM RESPONSE AVR response 20 ms Filed cur

8、rent to 90% 80 ms Machine Volts to 97% 300 ms EXTERNAL VOLTAGE ADJUSTMENT +/-10% with 1 k ohm 1 watt trimmer (see note 3) UNDER FREQUENCY PROTECTION Set point 95% Hz (see note 4) Slope 170% down to 30 Hz UNIT POWER DISSIPATION 10 watts maximum BUILD UP VOLTAGE 4 Volts AVR terminals ENVIRONMENTAL Vib

9、ration 20-100 Hz 50mm/sec 100Hz 2kHz 3.3g Operating temperature -40 to +70C Relative Humidity 0-70C 95% (see note 5) Storage temperature -55 to +80C NOTES 1. With 4% engine governing 2. After 10 minutes. 3. Applies to Mod status F onwards. Generator de-rate may apply. Check with factory. 4. Factory

10、set, semi-sealed, jumper selectable 5. Non condensing. DESIGN DETAIL TD_SX460.GB_05.03_02 The main functions of the AVR are: Potential Divider and Rectifier takes a proportion of the generator output voltage and attenuates it. This input chain of resistors includes the range potentiometer and hand t

11、rimmer which adjust the generator voltage. A rectifier converts the a.c. into d.c. for further processing. The Amplifier (Amp) compares the sensing voltage to the Reference Voltage and amplifies the difference (error) to provide a controlling signal for the power devices. The Ramp Generator and Leve

12、l Detector and Driver infinitely control the conduction period of the Power Control Devices and hence provides the excitation system with the required power to maintain the generator voltage within specified limits. The Stability Circuit provides adjustable negative ac feedback to ensure good steady

13、 state and transient performance of the control system. The Low Hz Detector measures the period of each electrical cycle and causes the reference voltage to be reduced approximately linearly with speed below a presettable threshold. A Light Emitting Diode gives indication of underspeed running. The

14、Synchronising circuit is used to keep the Ramp Generator and Low Hz Detector locked to the generator waveform period. The Low Pass Filter prevents distorted waveforms affecting the operation of the AVR. Power Control Devices vary the amount of exciter field current in response to the error signal pr

15、oduced by the Amplifier. Suppression components are included to prevent sub cycle voltage spikes damaging the AVR components and also to reduce the amount of conducted noise on the generator terminals. The Power Supply provides the required voltages for the AVR circuitry. SuppressionLow Pass FilterS

16、ynchronising Ciruit Low Hz Detection Power Control Devices Level Detector & Driver Reference Voltage Stability Circuit Potential Divider & Rectifier Power supplyRamp GeneratorGeneratorAmp Voltage Sensing Hand Trimmer Exciter Field FITTING AND OPERATING TD_SX460.GB_05.03_02 SUMMARY OF AVR CONTROLS CONTROL FUNCTION DIRECTION VOLTS TO ADJUST GENERATOR OUTPUT VOLTAGE CLOCKWISE INCREASES OUTPUT VOLTAGE STABILIT