1、 Modular I/O System Quick-Start Manual for ETHERNET Fieldbus Controller 750-872 Version 1.0.0 ii General WAGO I/O SYSTEM 750 ETHERNET StarterKit 2 Copyright 2008 by WAGO Kontakttechnik GmbH e.g., gold data contacts. 1.5 Scope of Validity This quick-start manual describes the programming of the 750-8

2、72 controller as the master of an outstation as defined by IEC 60870-5-101 and -104 with some basic modules from the WAGO-I/O-SYSTEM for telecontrol. Detailed information relating to handling, assembly and start-up is described in the “Ethernet TCP/IP 750-872“ and “WAGO-I/O-PRO CAA“ manuals. This do

3、cumentation is therefore only valid in conjunction with the appropriate manuals. Important Notes 7 Scope of Validity WAGO-I/O-SYSTEM 750 Telecontrol Quick-Start Manual Additional Information: You will find the “Ethernet TCP/IP 750-872“ and “WAGO-I/O-PRO CAA“ manuals on the “WAGO-I/O-PRO CAA“ CD (759

4、-911), on the “ELECTRONICC Tools 750-400; 750-501; 750-461; 750-600. Connect the 24V DC power unit to the supply (24V and 0V) for the controller and for the power contacts (see Fig. 1). For the application used in the example, it is sufficient to connect a jumper between “24V“ and “+“ and between “0

5、V“ and “-“. Fig. 1: Connections for the 750-872 controller Quick-Start Guide 9 Ethernet Network Start-Up WAGO-I/O-SYSTEM 750 Telecontrol Quick-Start Manual Fig. 2: Node with the 750-872 telecontrol fieldbus controller 2.2 Ethernet Network Start-Up The IP address is conveniently assigned using the se

6、rial programming cable provided and the “WAGO Ethernet Settings“ program. Connect your PC to the nodes configuration and programming interface. Install the “WAGO Ethernet Settings“ program. You will find it on the “Tools the network mask determines which bits belong to the network address and which

7、do not. Fig. 4: Setting the PC network address under Windows IP address : 192.168. 0. 44 SubNetMask : 255.255.255.0 Network address : 192.168. 0. Computer address: 44 Select a free computer address from the local network. You can identify the network address of your PC under “Start“ ? “Settings“ ? “

8、Network and Dial- up Connections“ ? “LAN Connection“ ? “Properties“. To do this, highlight the Internet protocol (TCP/IP) in the drop-down list box and press the “Properties“ button. NOTE: The double assignment of IP addresses can lead to serious network errors. 12 Quick-Start Guide Ethernet Network

9、 Start-Up WAGO-I/O-SYSTEM 750 Telecontrol Quick-Start Manual Switch to the “TCP/IP“ tab and enter an IP address for the node. Then transfer the change to the node with “Write“. Fig. 5: IP address settings for the 750-872 controller Now connect the node to the Ethernet network. Either directly with a

10、 crossover cable to a PC or with a 1-to-1 patch cable to a hub or switch. NOTE: Alternatively, the IP address for the controller can also be assigned with the “WAGO BootP Server“ instead of with “WAGO Ethernet Settings“. The address is assigned via the Ethernet interface on the device. A separate se

11、rial cable is not then necessary. However, the transferred IP address is only used temporarily. To save this permanently, the BootP protocol must also be deactivated in the Web-Based Management (WBM). To test the connection, open the “DOS Shell“ with “Start“ ? “Programs“ ? “Accessories“ ? “Input pro

12、mpt“ and set off a PING on the IP address of the node. Quick-Start Guide 13 Ethernet Network Start-Up WAGO-I/O-SYSTEM 750 Telecontrol Quick-Start Manual Fig. 6: Testing the connection to the 750-872 telecontrol controller with “PING“ If the node does not answer, please contact your network administr

13、ator. All settings can be viewed and changed using Web-Based Management (WBM). To use this, start your browser and enter http:/ in the URL line, followed by the IP address of the node (for example: http:/192.168.0.3). The integrated web server will then return the following website. Fig. 7: WEB serv

14、er homepage When a proxy server is used, this must be bypassed for local addresses. You will find information on bypassing the proxy server for local addresses in your browser Help under Proxy servers or LAN settings. 14 Quick-Start Guide Installing the WAGO Target System for CoDeSys WAGO-I/O-SYSTEM

15、 750 Telecontrol Quick-Start Manual The configuration sites linked via Hyperlinks require a login. In the default state the following users are defined: User Password admin wago user user guest guest Fig. 7: Users and passwords of the 750-849 controllers web server 2.3 Installing the WAGO Target Sys

16、tem for CoDeSys The following installation is only to be carried out when a CoDeSys version below 2.3.9.7 is used. From CoDeSys Version 2.3.9.7, the WAGO target system is already included in the installation. To install the WAGO target system, the installation file (Customer.exe) must first be downloaded and saved in any folder. The installation program must then be run by double-clicking on